IUC-X9-TXC & IUC-7X-RXC: Telephone Transmission System for 1 Analog Signal and 2 Digital Signals specsheet
|
Features:
- High Input-Output-Power Isolation (1500VAC Test)
- Industry Standard Inputs: 4-20 mA, 1-5 VDC, and more
- Industry Standard Output: 4-20 mA, 1-5 VDC, and more
- Send 1 Analog & 2 Digital Signals over Standard Class C Phone Line
- Channel Fail Contact
- Easy Field Calibration (Typ. calibration time < 2 min. using handheld meter only)
- Microprocessor Controlled for High Accuracy
- Two Wire Supply Option for Two Wire Transmitters
- Power: 117 VAC 50/60 Hz (Optional 24 VDC)
- High Noise Rejection
- CSA and NRTL Approved (LR 51078)
|
Function: The IUC-X9-TXC is a telephone line transmitter which takes in one of a number of standard analog signals and two dry contacts. It has a 600 Ohm impedance matched output which can connect directly into a class C telephone line. A frequency signal is sent to the IUC-7X-RXC telephone line receiver where it is converted back to an analog signal and two "C" Contacts. The IUC-7X-RXC also has an impedance matched input to allow direct connection to the phone line. A built in line monitor detects line failures and ramps the analog output to 0% or 100%.
Specifications:
- Isolation: Input to Output to Power 1500 VAC (test)
- Accuracy/Linearity: 0.3% max., 0.1% typ. (@ 20-100% Output)
- Operating Temperature: -40 Deg.C. to +50 Deg.C
- Temperature Effects: 0.5% max., 0.2% typ. (for 40 Deg.C. change)
- Loop Drive: Max. 1000 Ohms at 20mA
|
Manuals:
IUC-X9-TXC
IUC-7X-RXC
IUC-X9-TXC-N
IUC-7X-RXC-N | |